TT Systems

Last edit: 28/09/2026

TT Systems: the basics

In TT Systems all exposed-conductive-parts collectively protected by the same protective device shall be connected by the protective conductors to an earth electrode common to all those parts.

The neutral point, or the mid-point of the power supply system, shall be earthed. If a neutral point or mid-point is not available or not accessible, a line conductor shall be earthed.

TT Systems: how safety is guaranteed

In essence, also in TT systems, the connection to the PE conductor of exposed-conductive-parts has the aim of creating a Fault Loop. Compared with a TN system, in a TT system the fault loop is made in part of “dirty ground”. The issue is that the value of the fault current depends upon the “dirty ground” resistance. In Italy the resistance can be quite high (example 100Ω). In the Netherlands, especially in the polders, the resistance can be relatively low (a few ohms). That consideration is important.

In general, the standard allows the use of either RCD (Residual Current Devices) or of Overcurrent protective devices (like Miniature Circuit Breakers).

[IEC 60364-4-41] 411.5.2 Generally in TT systems, RCDs shall be used for fault protection. Alternatively, overcurrent protective devices may be used for fault protection  provided a suitably low value of Zs (see 411.5.4) is permanently and reliably assured.

In Italy the use of an RCD is compulsory.

In case a RCD is used, people are protected against Electric Shock by making sure the maximum voltage that a person can touch is not greater that 50 Vac.

[IEC 60364-4-41] 411.5 TT system. 411.5.3 Where a residual current protective device (RCD) is used for fault protection, the following conditions shall be fulfilled:
i) the disconnection time as required by 411.3.2.2 or 411.3.2.4, and
ii) RA x IΔn ≤ 50 V
where
– RA is the sum of the resistance in Ω of the earth electrode and the protective conductor for the exposed conductive-parts,
– IΔn is the rated residual operating current of the RCD.

It is also important to notice that, in case the measurement of the premise earth resistance (RA in the picture) is difficult, the standard allows the use of the fault loop impedance (that means ≈ RA + RN):

The reason why the voltage is limited to 50 Vac is that for voltages < 50 Vac the current flowing through the body is not dangerous.

TT System in North America

The TT system is widely used in Europe and many other parts of the world, whereas it is not normally used for conventional residential supplies in the United States and Canada, where an architecture corresponding, in IEC terminology, to a TN-C-S system is generally adopted.

The main difference concerns the earth-fault current path and the resulting protection principle. In North American residential supplies, the supply neutral (grounded conductor) is connected to the equipment grounding system at the service equipment. Downstream of this point, the neutral and equipment grounding conductors are kept separate. In the National Electrical Code (NEC), this connection is referred to as the system bonding jumper.

The connection between the neutral and the grounding system provides a low-impedance metallic path for the fault current, allowing it to return to the source and reach a sufficiently high value to cause the operation of overcurrent protective devices.

In a TT system, on the other hand, the fault current must pass through the earth to return to the source, flowing through the installation and source earth electrodes. The earth resistance therefore limits the fault current, which may be insufficient to cause the operation of overcurrent protective devices within the required disconnection time.

For this reason, protection against faults in TT systems generally relies on the use of residual current devices (RCDs). Their rated residual operating current must be coordinated with the earth resistance of the installation and the applicable disconnection-time requirements.

A further difference concerns protection against electric shock: in North America, Class A GFCIs used for this purpose typically operate in the 4–6 mA range, whereas in European installations RCDs with significantly higher rated residual operating currents are also used, depending on the specific protection required.