TT Systems

Last edit: 19/09/2026

TT Systems: the basics

In TT Systems all exposed-conductive-parts collectively protected by the same protective device shall be connected by the protective conductors to an earth electrode common to all those parts.

The neutral point, or the mid-point of the power supply system, shall be earthed. If a neutral point or mid-point is not available or not accessible, a line conductor shall be earthed.

TT Systems: how safety is guaranteed

In essence, also in TT systems, the connection to the PE conductor of exposed-conductive-parts has the aim of creating a Fault Loop. Compared with a TN system, in a TT system the fault loop is made in part of “dirty ground”. The issue is that the value of the fault current depends upon the “dirty ground” resistance. In Italy the resistance can be quite high (example 100Ω). In the Netherlands, especially in the polders, the resistance can be relatively low (a few ohms). That consideration is important.

In general, the standard allows the use of either RCD (Residual Current Devices) or of Overcurrent protective devices (like Miniature Circuit Breakers).

[IEC 60364-4-41] 411.5.2 Generally in TT systems, RCDs shall be used for fault protection. Alternatively, overcurrent protective devices may be used for fault protection  provided a suitably low value of Zs (see 411.5.4) is permanently and reliably assured.

In Italy the use of an RCD is compulsory.

In case a RCD is used, people are protected against Electric Shock by making sure the maximum voltage that a person can touch is not greater that 50 Vac.

[IEC 60364-4-41] 411.5 TT system. 411.5.3 Where a residual current protective device (RCD) is used for fault protection, the following conditions shall be fulfilled:
i) the disconnection time as required by 411.3.2.2 or 411.3.2.4, and
ii) RA x IΔn ≤ 50 V
where
– RA is the sum of the resistance in Ω of the earth electrode and the protective conductor for the exposed conductive-parts,
– IΔn is the rated residual operating current of the RCD.

It is also important to notice that, in case the measurement of the premise earth resistance (RA in the picture) is difficult, the standard allows the use of the fault loop impedance (that means ≈ RA + RN):

The reason why the voltage is limited to 50 Vac is that for voltages < 50 Vac the current flowing through the body is not dangerous.